A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.3), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.3). The web server interface of affected devices improperly processes incoming malformed HTTP traffic at high rate. This could allow an unauthenticated remote attacker to force the device entering the stop/defect state, thus creating a denial of service condition.
Problem types
CWE-20: Improper Input Validation
Product status
Any version before V2.0.3
Any version before V2.0.3
References
cert-portal.siemens.com/productcert/html/ssa-625789.html