A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.

PUBLISHED Reserved 2025-08-14 | Published 2025-08-14 | Updated 2025-08-14 | Assigner Rockwell




HIGH: 8.7CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N

Problem types

CWE-1287: Improper Validation of Specified Type of Input

Product status

Default status
unaffected

Version 2.011 or below
affected

References

www.rockwellautomation.com/...dvisories/advisory.SD1737.html